Troubleshooting
The setup code is lost
Start pvmon again. If no account exists, pvmon writes a new code to the log.
A password is lost
Stop pvmon.
Set a new password:
bashprintf '%s\n' "$PASSWORD" | pvmon user reset-password admin
The web interface cannot change a setting
config.yaml or an environment variable defines the setting. Change it there.
pvmon does not start
- Read the log. pvmon shows each configuration error with the path of the key, for example
meters.grid.device: unknown device "meterr". - Correct the errors.
- Run
pvmon config validate.
A Modbus device reports "illegal data address"
Set read: direct for this device.
A Modbus device is offline frequently
Many gateways and RS485 buses can answer only one request at a time.
- Give all devices of one bus the same connection.
- Increase the poll interval.
- Make sure that no other program reads the device.
Import and export are higher than on the utility meter
Refer to Grid netting.
A day shows n/m days or the mark ≈
Refer to Energy and data quality.
The browser cannot install the app
The browser must use HTTPS or localhost.